D-C402 Conventional Rate of Rise and Fixed Temperature Heat Detector is non-addressable. With built-in microprocessor, it works stably with reliable fixed fire judging program. Used together with an active end of line unit (AEOL), it can connect with compatible control panels to process fire alarm signals.
Operating Voltage | 24VDC(12VDC~28VDC) |
---|---|
Standby Current | ≤60µA |
Alarm Current | 10mA≤I≤30mA |
Indicators | Red. Quiet in normal condition. Illuminates steadily in alarm. |
Remote Indication Output | Directly connecting with remote indicator (built-in 2kΩ resistor in series,). Quiet in normal condition. Illuminates steadily in alarm. |
Maximum Ripple Voltage | 4V (peak-to-peak value) |
Alarm Clear | Instantaneous Power-off (5s Max., 2.5VDC Max.) |
Power-up Time | ≤10s |
Action Temperature | 58°C |
Class | A1R |
Wiring | Polarized 2-core for detection zone cable. Polarized 2-core for remote indicator. |
Operating Temperature | -10°C to +50°C |
Relative Humidity | ≤95%, non condensing |
Ingress Protection Rating | IP33 |
Material and Color of Enclosure | ABS, white (RAL9016) |
Dimensions | Diameter: 100mm Height: 58mm (with base) |
Mounting Hole Distance | 45mm~75mm |
Weight | About 120g |
Contact us about Heat Detector: