Conventional Control Panel (8/16 Zones)

The P-C208A/216A conventional fire control panels provide eight/sixteen zones of fire detection. Panels have been designed to offer high standards of performance, reliability and quantity and comply fully with BS5839, Part 4, 1988 and EN 54 parts 2 and 4. (Each zone can be connected with 15 conventional fire detectors and infinite no of MCB when using Active EOL).


Part Number P-C208A P-C216A
Operating Voltage 220VAC ± 15%, 50Hz
Standard BS5839, Part 4, 1988 and EN 54 parts 2 and 4
Approval CE, LPCB
Operating Temperature -10°C to 40°C @95% relative humidity
Number of Zones 8 Zone 16 Zone
Zone Capacity 15 detectors (AOL); 25 detectors (EOLR)
Standby Batteries 7 AH, 24hours monitoring state
Output Voltage 20VDC to 28VDC
Static Loading Current 2.4 mA (when connected with 15 conventional detector)
Fire Alarming Resistance 150Ω-1.5kΩ (normal 470Ω)
End of Line Resistor 4.7kΩ or AEOL (Active End Of Line)
No. of Sounder Output 4
Sounder Output Output voltage: 20VDC ~ 28VDC; Output Current: 1A
Fire Alarm Output Output voltage: 20VDC ~ 28VDC; Output Current: 0.5A
Fault Output Capacity Passive contact output: 24VDC / 1A
Aux. Power Output 20VDC to 28VDC, 0.5A
Application Indoor Use
Materials and Colour Coated Metal / Grey
Dimension 380mm x 95mm x 320mm
  • Microprocessor controlled SMT Electronics
  • Compliant with EN54 part 2&4, & BS5839, Part 4, 1988
  • Repeater Panel Interface
  • Both end of line resistors and active end of line can be used.
  • Programmable sounder circuits outputs
  • Zone Isolate / Test control
  • Fully monitored sounder circuits
  • Key control evacuate over-ride
  • Fire alarm output for remote control
  • Class change terminals for remote control
  • Up to 15 fire detectors and infinite manuals call points each zone.