AHS-9315 – Combination Smoke And Heat Detector
Multi-purpose Design: when there is smoke or heat during pre-fire period, field situation will vary due to different environments. This combination design is to ensure that the pre-fire confirmation will not be affected by varying environments.
Categories: | Fire Alarm Detectors, Fire Alarm System |
---|
FEATURES
- Multi-purpose Design: when there is smoke or heat during pre-fire period, field situation will vary due to different environments. This combination design is to ensure that the pre-fire confirmation will not be affected by varying environments.
- Smoke gate has a special design to obscure the strong light effectively and allow smoke to come in easily. Water vapor will not gather on the insect guard screen to cause a false alarm.
- Features an accumulated water discharger to eliminate leakage of water from the water pipes or ceiling which may leak into the detector and cause a false alarm.
- This detector has passed strict quality control and repetitive testing, hence its quality is stable and highly reliable.
SPECIFICATION
Model |
AH-9315
|
||
Type |
2-wire
|
3-wire
|
4-wire
|
Alarm Contact |
N/A
|
N/A
|
0.8A @30V DC
0.4A @125V AC |
Voltage Range |
12 ~ 30V DC
|
||
Alarm Current @24V DC 470Ω |
35mA
|
35mA
|
30mA
|
Standby Current |
20 ~ 30μA (Loop response under 75μA)
|
||
Sensitivity Setting |
Comply to EN54
|
||
Thermal Setting |
55℃
|
||
Ambient Temperature |
-10℃ ~ +55℃
|
||
Material |
Fire-proof plastic
|
||
Dimensions |
111mm(Dia.) x 50mm(H)
|
||
Weight |
About 170g
|
||
Color |
White
|
Effective alert area
Building Height |
Area Covered
|
Under 4M |
150 M2
|
4 ~ 20M |
75 M2
|
Tour Reviews