AHR-871 Mechanical Rate Of Rise Heat Detector

Heat-sensing diaphragm can operate for unlimited number of times and is not affected by room temperature. The conducting parts use gold coating to avoid oxidation.

Categories:,
FEATURES 
  • Heat-sensing diaphragm can operate for unlimited number of times and is not affected by room temperature. The conducting parts use gold coating to avoid oxidation.
  • Uses alloy air equalizer to avoid humidity and stabilize the ventilation function. Alloy itself has many micro-holes that can expel non-fire heat to avoid false alarms.
  • The unit is completely sealed; its function is not affected by humidity, dust or insects.
  • This detector has passed strict quality control through automatic repetitive testing and been calibrated automatically under stable temperature and humidity conditions. Thus, quality and reliability are consistent from the first detector produced to millionth.

 

SPECIFICATION
Model
AHR-871
Type
2-wire
3-wire
4-wire
Alarm Contact
N/A
N/A
0.8A @30V DC
0.4A @125V AC
Voltage Range
12 ~ 30V DC
Alarm Current
@24V DC 470Ω
40mA
40mA
35mA
Alarm Temperature
Comply to EN54, CNS
Ambient Temperature
0℃ ~ +55℃
Material
Fire-proof plastic
Dimensions
111mm(Dia.) x 45mm(H)
Weight
About 130g
Color
White

Effective alert area

Construction/Height
Under 4M
4M ~ 8M
Fire-proof Building
90 M2
45 M2
Ordinary Building
50 M2
30 M2