select language:D-C401 Conventional Photoelectric Smoke Detector is non-addressable. Used together with end of line unit, it can connect with compatible control panels to process detection signals.
| Operating Voltage | 24VDC (12VDC~28VDC) |
|---|---|
| Standby Current | ≤60µA |
| Alarm Current | 10mA≤I≤30mA |
| Indicators | Red. Quiet in normal condition. Illuminates steadily in alarm. |
| Remote Indicator Output | Directly connecting with LED (built-in 2k resistor in series). Quiet in normal condition. Illuminates steadily in alarm. |
| Maximum Ripple Voltage | 4V (peak-to-peak value) |
| Alarm Clear | Instantaneous Power-off (5s Max., 2.5VDC Max.) |
| Power-up Time | ≤10s |
| Max. Wind Speed | 7.6m/s (1500fpm) |
| Wiring | Polarized 2-core for detection zone cable. Polarized 2-core for remote indicator. |
| Ambient Temperature | -10°C to +50°C |
| Relative Humidity | ≤95%, non condensing |
| Ingress Protection Rating | IP23 |
| Material and Color of Enclosure | ABS, white (RAL9016) |
| Dimensions | Diameter: 100mm Height: 56mm (with base) |
| Mounting Hole Distance | 45mm~75mm |
| Weight | About 120g |